End to End Beam Detector
DESCRIPTION
The SHIELD Alpha 3000 End to End infrared Optical Beam Smoke Detector (OBSD) has been designed using the latest optical technology, incorporating modern industrial, electronic and software techniques. This detector offers cost effective protection of large, open area spaces with high ceilings. It is also very suited to applications where access to ceiling mounted smoke detectors presents practical difficulties.
The SHIELD Alpha 3000 is ideal for applications where line of sight for the IR (infra-red) detection path is narrow and where the building structure uses reflective surfaces. It has also been designed to be aesthetically pleasing and thus can equally suit modern architectural buildings as well as historical sites, particularly where ornate ceilings exist.
SPECIFICATION
Operating Range | 5 – 120 m |
---|---|
Operating Voltage Range | 12 to 36 VDC ±10% |
Operating Controller Current (with 1 or 2 Receivers) | 14 mA (constant) |
Operating Transmitter Current | 8 mA (per Transmitter) |
Power Down Reset Time | >20 seconds |
Fire and Fault Relay Contacts | Resistive VFCO 2A @ 30 VDC |
Operating Temp. (non-condensing) | -20°C to +55°C |
Optical Wavelength | 850 nm |
IP Rating | IP54 |
Relative Humidity (non-condensing) | 93% |
Dimension (W x H x L) & Weight | |
Control Unit | 203 mm x 124 mm x 71 mm, 600 g |
Transmitter & Receiver | 78 mm x 77 mm x 161 mm, 200 g |
FEATURES
- Separate Transmitter and Receiver Heads
- Range 5 m to 120 m, configurable per set of Detectors
- Lateral Spacing per NFPA 72 is 18 m
- Integral Laser Alignment in Receiver
- 2-wire Interface between Controller and Receiver
- Single and Twin Channel capability
- Separate Fire and Fault Relays per Detector
- Low Level Controller with LCD display
- Programmable Sensitivity and Fire Threshold
- Automatic Gain Control (AGC) for drift compensation
- Built-in electronic UL/ULC obscuration-acceptance fire test
- Knockouts for ease of installation and wiring
- Optional Transmitter powering from Controller
Multisensor Detector
DESCRIPTION
SHIELD Photo-Electric Smoke Detector works on the light-scatter principle and is ideal for applications where slow-burning or smoldering fires are likely.
FEATURES
- Responds well to slow-burning, smoldering fires
- Well suited for bedrooms and escape routes
- Unaffected by atmospheric pressure
Smoke Detector
DESCRIPTION
SHIELD Photo-Electric Smoke Detector works on the light-scatter principle and is ideal for applications where slow-burning or smoldering fires are likely.
FEATURES
- Responds well to slow-burning, smoldering fires
- Well suited for bedrooms and escape routes
- Unaffected by atmospheric pressure
Heat Detector
DESCRIPTION
SHIELD Heat Detector is distinguishable by the low airflow resistant case and uses a single thermistor to sense the air temperature around the detector.
FEATURES
- Ideal for environments that are dirty or smoky under normal conditions
- Well suited for warehouses, loading docks and parking garages
- Unaffected by wind or atmospheric pressure
- Remote test feature
Repeater Panel
DESCRIPTION
Designed and manufactured to the highest standards in a quality controlled environment the SHIELD Omega-R fire alarm reporter provides a simple and convenient method of extending thecontrols and indications of the SHIELD Omega fire alarm control panel to other locations.
The large, graphic liquid crystal display and high brightness LED indicators duplicate the indications on the SHIELD Omega fire alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection.
The SHIELD Omega-R is powered by 24V DC (which can be via an additional 2 conductors from the control panel or local 24V DC listed supply).
SHIELD Omega-R is housed in a small enclosure which is styled similarly to the SHIELD Omega control panel and is ideal for installations where a large control panel would be detrimental décor such as entrance halls.
Up to 15 SHIELD Omega-R annunciators can be connected to each control panel on the Omega network making Omega-R ideal where multiple points of indication and/or control are required such as nurses stations or shop units.
FEATURES
- Available in Red
- Up to 15 annunciators can be connected to each SHIELD Omega fire control panel
- Large liquid crystal display (240×64 pixels)
- High brightness LED indications
- Internal sounder
- Replicates all panel controls
- Simple, two-wire serial connection
- Small, style enclosure
- Removable electronics for easy installation
- 24V DC powered
- Low power consumption
- Multi language options
- Connection supervised by SHIELD Omega fire control panel
Analog Control Panel (2 or 4 Loops)
DESCRIPTION
Designed and manufactured to the highest standards in a quality controlled environment the SHIELD Omega-R fire alarm reporter provides a simple and convenient method of extending thecontrols and indications of the SHIELD Omega fire alarm control panel to other locations.
FEATURES
- Available in Red
- Up to 15 annunciators can be connected to each SHIELD Omega fire control panel
- Large liquid crystal display (240×64 pixels)
- High brightness LED indications
- Internal sounder
- Replicates all panel controls
- Simple, two-wire serial connection
- Small, style enclosure
- Removable electronics for easy installation
- 24V DC powered
- Low power consumption
- Multi language options
- Connection supervised by SHIELD Omega fire control panel
Analog Control Panel (1 or 2 Loops)
DESCRIPTION
The SA-P20R and SA-P4LR analog addressable FACP supports 2 or 4 SLC loops for a total of 500 primary points or 800 points using subpoints. SLC loop communications uses standard twisted pair cabling, shielded cable is not necessary.
The panel may be configured with various communication cards; Communications options support central station monitoring, Virtual Panel, and networking.
The Panel can be configured as a stand alone panel with just a few devices for a small building, it can also operate as the building system and can be part of a network with a total of 64 nodes serving a multiple building campus or a very large facility.
Auto Learn capability provides a convenient method to troubleshoot new installations before final programming is loaded
FEATURES
- UL 864 9th Edition listed
- Multi-Loop 2 Analog Addressable
- Loops Field upgradable to 4
- 126 primary points per loop
- Powerful, network wide cause and effects (500 total). Fully user programmable by point or zone
- 800 points per panel when using devices with sub-points
- Up to 10,000 ft. wiring length on SLC loop
- 64 Panels on a network
- Programmable through a PC connection to the panel, or through keypad
- Programmable relays – 5
- Supervised Powered Outputs – 3
- Programmable notification appliance circuits:4
- Power per NAC: 1.6 Amps Max
- Programmable outputs on SLC loop
- Programmable Function button on front display
- Fire Drill button on front display
- Day and night sensitivity settings (user programmable)
- Power Supply: 5.25 Amp, regulated & integrated
- LCD Display: 8×40
- Zonal Mode: Annunciation by zone w/o individual relationships
- Panel Ring Modes: Common, Zonal, and Stage 2
- NAC Outputs programmable as Continuous, March, Temporal
- Program cause and effects AND, OR, or any two (Cross Zone)
- Battery size: Up to 17 Ah in standard enclosure; up to 52 Ah with external cabinet
- Access levels: 3
- Access key switch: Yes
- Recognized for use in High Rise
- One-man walk test – Fire Test Mode
- Available in Red
Foam Trolley
DESCRIPTION
NAFFCO Foam Master is a self contained mobile foam unit which has been specially developed for the rapid deployment of foam extinguishing agent to fires and chemical spills. NAFFCO Foam Master can be operated by one person.
This unit is an ideal choice for the protection of smaller flammable liquid hazards such as boiler rooms, oil storage loading terminals and industrial sites.
SPECIFICATION
Model No. | NFM 150L | NFM 500 |
---|---|---|
Foam Tank Capacity | 150 Liters | 500 Liters |
Foam Tank Material | Stainless Steel (S.S.316 L) | Stainless Steel (S.S.316 L) |
Foam Inductor | 2″, 1-6% Variable | 2 1/2″, 1-6% Variable |
Foam Branch Pipe with ball valve | 2″ | 2″ |
Fire Hose | 1 1/2″ Dia 15M (2Nos) | 2 1/2″ dia, 30m (2nos) |
Wheels | Solid Rubber | R-13 Type |
Special Foam Nozzles and Branch pipes available as per request. Higher capacities available as per request.
Medium Expansion Foam Branch Pipes
DESCRIPTION
Medium Expansion Foam Branch pipes are designed to produce large qualities of foam in situations requiring rapid foam cover with low water usage. It has the advantage of producing five times more foam with the same amount of water than compared to Low Expansion Foam Branch pipes.
SPECIFICATION
- Nominal Size : NFB – 25,NFB – 40
- Flow Rate : 250 LPM,400 LPM @ 7 BAR
- Expansion Rate : 50
- Effective Reach : 6 To 8 Meters
- Effective Reach : 1 ½” BS Male (Instantaneous)
Foam Sprinkler Head
DECSCRIPTION
Naffco Foam Sprinkler Heads Mounted within the roof structure provides an even distribution of foam assuring fast flame knock down and fire control. They also provide cooling to the structure and protection from heat radiation.
SPECIFICATION
Model No. | Size | Spray Pattern | Flow Rate | Material |
---|---|---|---|---|
NH-500 | 1/2″ NPT | Upright/Pendent | 61 – 111 LPM (as per UL) 136 LPM (as per FM) | Brass Stainless Steel |
NH-520 | 1/2″ NPT | Pendent | 31 gpm | Brass Chrome Finish |
NH-550 | 3/4″ NPT | Pendent | 50 gpm | Brass Chrome Finish |
SD1010 | 1/2″ NPT | Pendent | 12.2 Lpm/m² | Brass |
Ratio Controller
DESCRIPTION
Pressure Propotioner is used to produce constant preset foam solution in pressure proportioning systems. It is designed to inject automatically the correct quantity of foam concentrate into a water stream over a wide flow rates by balancing the pressure of the foam concentrate with that of the water supply.
SPECIFICATION
Size | Flow Rate (LPM) | |||
---|---|---|---|---|
AFFF 3% (as per UL) | AFFF 3% (as per FM) | AFFF 6% (as per FM) | ARAFFF 3% | |
65 NB | 100 – 1550 | 78 – 1036 | 159 – 984 | 380 – 500 |
80 NB | 260 – 3000 | 270 – 3000 | 270 – 3000 | 680 – 2900 |
100 NB | 650 – 6000 | 660 – 5750 | 633 – 3922 | 1400 – 5800 |
150 NB | 1200 – 12000 | 1090 – 9530 | 674 – 4012 | 2750 – 11600 |
In-line Foam Inductor
DESCRIPTION
Line Proportioner offers a simple accurate method of proportioning when the water supply pressure is reasonably high. Each proportioner is designed for a set water pressure. However, higher or lower inlet pressure results in an increase or decrease in water flow with a change in proportioning.
SPECIFICATION
Model | Type | Performance |
---|---|---|
NF-350B-225 (V) | Portable | 225lpm@100psi |
NF-350B-450 (V) | Portable | 450lpm@100psi |
NF-350B-600F | Fixed | 600lpm@100psi |
NF-350B (V) | Variable | 386lpm (100gpm) ±5% |
NF-350B (F) | Fixed | 386lpm (100gpm) ±5% |