021-35866991-2 | 021-35800017-18

DESCRIPTION

Certified by LPCB to meet fire test Standards – BS EN 50200:2006 + Annex E 30 minutes, BS EN 50200 PH30, PH60 & PH120 & BS 6387 CWZ. It is also fully approved to the Low Smoke & Zero Halogen requirements detailed by BS 5839-:2013 & BS7629-1:2008.

Shield ‘Premium’ Cable retains continuity for 30 minutes under fire conditions at 830°C, this demanding fire cable test includes a final 15 minutes under fire & water spray conditions while a mechanical shock is applied every 5 minutes throughout the full 30 minute test.

Catalogue

SPECIFICATION

LPCB approved toFire Resistance StandardBS EN 50200:2006 +Annex E 30 mins
Fire Resistance StandardBS EN 50200:2006 PH120
Fire Resistance StandardBS 6387:1994 Clause 11 CWZ
Halogen Emission StandardBS EN 50267-2-1:1999
Halogen Emission StandardBS EN 61034-2:2005
Also for use withEmergency LightingBS 5266-1:2005
Voice Alarm Systems StandardBS 5839-8:2008
Voice Communication StandardBS 5839-9:2003
(Risk Assessment May Demand Mechanical Protection)
MaterialsDrain Wire0.80mm Dia (0.50mm2) Tinned Copper
ConductorsPlain Annealed Copper
Core InstallationFire Resistant ZHLS Silicone
ScreeningAluminium Foil
Outer SheathLow Smoke Halogen Free Thermoplastic
Working VoltageCore to Core500V
Core to CPC300V
TypesOuter Sheath ColoursRed, White or Black
Number of Cores2, 3 & 4 Core
Inner Cores CSA1.0, 1.5, 2.5 & 4.0mm CSA
Resistance1.0mm CSA18.1 Ohms / 1 Km
1.5mm CSA12.1 Ohms / 1 Km
2.5mm CSA7.41 Ohms / 1 Km
4.0mm CSA4.61 Ohms / 1 Km
Minimum Bend RadiusRadius = 6 x Diameter
Operating Temp.Minimum/Maximum-40°C to +90°C
Installation Temp.Minimum/Maximum0°C to +70°C
Voltage Drop
(DC or Single Phase AC)
1.0mm CSA44 Ohms mV / A / m
1.5mm CSA29 Ohms mV / A / m
2.5mm CSA18 Ohms mV / A / m
Approximate
Overall Diameter
2 Core1.0mm / 7.15mm
1.5mm / 7.40mm
2.5mm / 8.70mm
3 Core1.0mm / 7.75mm
1.5mm / 8.55mm
2.5mm / 9.20mm
4 Core1.0mm / 8.00mm
1.5mm / 8.80mm
2.5mm / 11.10mm
Approximate
Weights
2 Core with CPC1.0mm – 8.0 Kg / 100 m
1.5mm – 9.5 Kg / 100 m
2.5mm – 14.1 Kg / 100 m
3 Core with CPC1.0mm – 9.5 Kg / 100 m
1.5mm – 12.9 Kg / 100 m
2.5mm – 19.1 Kg / 100 m
4 Core with CPC1.0mm – 10.9 Kg / 100 m
1.5mm – 14.5 Kg / 100 m
2.5mm – 22.2 Kg / 100 m
Current Rating
(Current Ratings listed are at 30°C
Refer to BS7671/EE Wiring
Regulations for de-rating factor.)
Cable Clipped
(DC or Single Phase AC)
1.0mm 15A
1.5mm 19.5A
2.5mm 27A
Enclosed
(DC or Single Phase AC)
1.0mm 13A
1.5mm 16.5A
2.5mm 23A
Insulation Resistance10MÙ> at 5000V d.c.

FEATURES

  • Reduced Installation time and costs
  • Easy to install and Superb Working Flexibility
  • All in one – Easy to Strip Outer Sheath
  • No Separate Foil
  • No Additional Fibre Wraps
  • No mica tape on conductors
  • No additional core separators to remove
  • Cable Construction Provides High Level Data Protection