DESCRIPTION

NAFFCO Fire hose racks are designed for use in controlling incipient fire by building occupant use and conform to NFPA 14 standards for CLASS II service. The Fire Hose Racks are manufactured to comply UL & FM standard.

SPECIFICATION

ModelNHR 38V*NHR 64V
FIRE HOSE
Fire Hose TypeSingle jacket, Light weight
Thermoplastic lining with high tenacity
filament polyester yarn, UL listed
Single jacket, Light weight
Thermoplastic lining with high tenacity
filament polyester yarn, UL listed
Size & Color1½” x 30Mtr., White2½” x 30Mtr., White
Service Pressure250 PSI250 PSI
Proof Pressure500 PSI500 PSI
Burst Pressure750 PSI750 PSI
COUPLINGS
Type1-1½” NH Female Threaded Coupling,
Brass
2-½” NH Female Threaded Coupling,
Brass
ANGLE VALVE
Working Pressure300 PSI300 PSI
Test Pressure600 PSI600 PSI
NOZZLE
Inlet Size1.5″ Female NST Threaded2.5″ Female NST Threaded
Discharge rate
(in full spray pattern)
130±5GPM @ 100PSI205±5GPM @ 100PSI

Pressure reducing valve available upon request with FM approved rack assembly.
*UL/FM Approved

FEATURES

  • Hose rack frame material made of Stainless Steel Gr.304.
  • Provides an immediate water source for fire suppression.
  • Easy individual operation.
  • Max. Service pressure of the Fire Hose Rack Assembly up to 150psi.
  • Hose rack is designed to hold the hose with movable pins for easy & quick operation at the time of Emergency.
  • An automatic release mechanism allows water to flow through the hose after removal of the hose and nozzle.
  • Standard assemblies include:
    • Angle Valve or pressure reducing type valve (UL/FM approved)
    • Hose Rack frame material made of stainless steel
      • Brush Finish
      • Mirror Finish
      • RED (RAL 3000) Powder Coated Oven Baked
    • Hose rack frame
    • Hose rack nipple
    • Hose coupling
    • Fire Hose – 30 Mtr. (UL Listed)
    • Fog nozzle. (UL approved)