Horizontal and Vertical Bladder Tank Pre-Piped
DESCRIPTION
NAFFCO Pre-piped Bladder Tank is a complete self-contained proportioning system consisting of a bladder tank, ratio controller, and assembled piping. It is designed to inject foam concentrate into the water supply of a fire protection system and automatically proportions over a wide range of flow and pressures without the use of external power supply.
SPECIFICATION
Tank Shell | Carbon Steel, SA 516 Gr.70. |
---|---|
Bladder | Vinyl Based Polymer |
Pressure Relief Valve (Optional) | Brass Construction with Set Pressure @ 15 bar |
Internal Piping | Perforated PVC, sch. 80. |
Flanges | ASTM A105, Class 150 |
Water Pipe | Carbon Steel. sch. 40. |
Foam Pipes | Stainless Steel. sch. 40. |
Vent/Drain/NRV Valves | Brass/Bronze |
Sight Glass Valve | Sight Gauge with Shut Off & Drain Valve |
Painting External | Zinc Rich Primer with Red Enamel Finish |
Painting Internal | Zinc Rich Primer with Coal Tar Epoxy Paint |
FEATURES
- Require less space than foam pump skid
- Designed for maximum agent discharge
- Permanently welded lifting lugs for easy tank movement and positioning
- Tanks are Externally Red enamel coated and
- Internally Coal tar Epoxy coated.
Fluoroprotein Foam (FP) Concentrate
DESCRIPTION
NAFFCO FLUOROFOAM is a fluoroprotein foam concentrate containing C6 flourinated surfactants in a carefully formulated protein foam liquid base. This ensures the production of a stabilised fluid foam which will cover a burning hydrocarbon fuel surface very rapidly. The water soluble fluorosurfactant makes the foam hydrocarbon repellent and reduces the amount of burning particles absorbed by the foam in fighting the hydrocarbon fuel fires. Once fire extinction has been achieved the high stability of the foam blanket ensures against the risk of re-ignition and provides excellent protection against “burn-back” should any inaccessible pockets of fire remains.
SPECIFICATION
Model | 3PUL-C6 – FP 3% | 6PUL – FP 6% |
---|---|---|
Product | Fluoroprotein Foam | Fluoroprotein Foam |
Appearance | Dark Brown Liquid | Dark Brown Liquid |
Use Concentration | 3% | 6% |
Specific Gravity @ 25°C | 1.13 ± 0.02 | 1.09 ± 0.02 |
pH @ 25°C | 7.0 ± 0.5 | 7.0 ± 0.5 |
Viscosity @ 25°C | < 20 cSt | < 20 cSt |
Suspended sediment (v/v) | < 0.3% | < 0.3% |
Pour Point | Flows at -7°C | Flows at -7°C |
*Foam Expansion | > 6 | > 6 |
*Foam Drainage 25% | 3 minutes 30 secs. | 5 minutes |
Film Forming Fluoroprotein Foam (FFFP) Concentrate
DESCRIPTION
NAFFCO FLUOROFOAM FFFP3AF and FFFP6AF are Film Forming Fluoroprotein Foam concentrates (FFFP) containing hydrolyzed protein and preservatives, together with a blend of fluorinated surfactants to achieve the maximum synergistic effect. The blend of flurochemicals selected is effective in reducing the surface tension of water as well as the interfacial tension between water and oil sufficiently low to give stable film on the surface of the fuel and as a result produce fire extinguishing rates superior to those obtained with synthetic based compounds.
SPECIFICATION
Model | FFFP3AF – FFFP 3% | FFFP6AF – FFFP 6% |
---|---|---|
Product | FFFP | FFFP |
Use Concentration | 3% | 6% |
Specific Gravity @ 25°C | 1.17 ± 0.03 | 1.15 ± 0.03 |
pH @ 25°C | 6.5 – 7.5 | 6.5 – 7.5 |
Viscosity @ 25°C | < 30 cSt | < 30 cSt |
Suspended sediment (v/v) | < 0.1% | < 0.1% |
Freezing Point | -16°C | -16°C |
Pour Point | -15°C | -15°C |
Storage temperature | -15°C – +49°C | -15°C – +49°C |
Foam Expansion | > 8 | > 8 |
Foam Drainage 25% | 3.5 minutes min. | 3.5 minutes min. |
Eco Barid Foam
DESCRIPTION
NAFFCO ECO BARID FOAM is high quality fluorine free foam which can be used at 1% to 6% concentration for different application. It can be used to extinguish fires caused by polar or hydrocarbon fuels. In addition to this ECO BARID is capable of extinguishing A, B, D & F CLASSES of fire and is suitable for the use with most types of proportioning & discharge devices andperforms excellently well when used with CAF systems. ECO BARID FOAM is 100% environmental friendly free from PFOA, PFOS & fluorine.
FEATURES
- Excellent wetting characteristics when used in combating Class A fuel type of fires
- If inadvertently frozen, thawing will render product completely serviceable again
- It is mostly suitable for use with medium and high expansion foam generators
Class A Foam
DESCRIPTION
NAFFCO Class A Foam is an non-corrosive, non-toxic, biodegradable Class A fire fighting foam concentrate. When mixed with water in the correct proportion, it changes the properties of water; it reduces the surface tension of the water, and produces foam which allows the water to cling to vertical or horizontal surfaces without run off. This allows the water to absorb more heat and provides greater penetration into Class A fuels.
SPECIFICATION
Product | Class A Foam |
---|---|
Use Concentration | 0.1% – 1.0% |
Specific Gravity @ 25°C | 1.02 – 1.06 |
pH | 6.5 – 8.5 |
Viscosity | < 20 cSt |
Suspended sediment | None |
FEATURES
- Water treated with Class A Foam concentrate is 3 to 5 times more effective to fight fire on Class A fires than untreated water
- Water treated with Class A Foam concentrate will wet Class A fuels up to 20 times more efficiently than untreated water
- Suitable for use with either fresh or salt water
- Suitable for used with non-air-aspirating or aspirating hand line nozzles
- Suitable for use with Compressed Air Foam Systems (CAFS)
- Suitable for use on rubber (tires), coal, paper, and many other types of Class A fuels
- Suitable for use through medium expansion nozzles on Class A or contained Class B flammable liquids.
Aqueous Film Forming Foam (AFFF) Concentrate
DESCRIPTION
NAFFCO FILMPLUS are superior quality Aqueous Film Forming Foam concentrate which can be used to extinguish fires of non-polar hydrocarbon fuels. FILMPLUS is suitable for use with most types of proportioning and discharge equipment.
AFFF foam concentrate are designed for rapid fire knockdown by producing a thin aqueous film which helps to prevent the release of fuel vapours. The foam blanket, from which the film forming liquid drains separates oxygen from the fuel surface, extinguishes the fire and prevents re-ignition. The water content of the foam provides a cooling effect.
SPECIFICATION
Model | NF1UL-C6 – AFFF 1% | NF3 F-C6 – AFFF 3% | NF3UL – AFFF 3% | NF6UL – AFFF 6% |
---|---|---|---|---|
Product | AFFF | AFFF | AFFF | AFFF |
Use Concentration | 1% | 3% | 3% | 6% |
Specific Gravity @ 20°C | 1.04 ± 0.02 | 1.02 ± 0.02 | 1.02 ± 0.02 | 1.02 ± 0.02 |
pH @ 20°C | 8.0 ± 1.0 | 8.0 ± 1.0 | 8.0 ± 1.0 | 8.0 ± 1.0 |
Viscosity @ 20°C | < 10 cSt | < 5 cSt | < 5 cSt | < 5 cSt |
Pour Point | Flows at -8°C | Flows at 0°C | Flows at 0°C | Flows at 0°C |
*Foam Expansion | > 7 | > 7 | > 7 | > 7 |
*Foam Drainage 25% | 2 minutes min. | 2 minutes min. | 2 minutes min. | 2 minutes min. |
Expansion & Drainage values depend on the equipment & the application conditions
Alcohol Resistant Aqueous Film Forming Foam (AR-AFFF) Concentrate
DESCRIPTION
FILMPLUS AR is a new generation of Alcohol Resistant Aqueous Film Forming Foam Concentrate based on C6 fluorosurfactants which are safer to the environment when fighting hydrocarbon and polar solvent fires.
The film forming characteristics of FILMPLUS AR means that it spreads rapidly across a fire. As a result, it is highly effective against hydrocarbon fires and with the addition of special polymers it is also highly effective against polar solvents. When used in an emergency, it generates a free flowing cohesive foam blanket with excellent burn back resistance.
SPECIFICATION
Model | AR-AFFF 1X3% | AR-AFFF 3X3% | AR-AFFF 3X6% |
---|---|---|---|
Product | AR-AFFF | AR-AFFF | AR-AFFF |
Use Concentration | 1% on hydrocarbons & 3% on polar solvents | 3 % on hydrocarbons and polar solvents | 3% on hydrocarbons & 6% on polar solvents |
Specific Gravity @ 20°C | 1.05 ± 0.02 | 1.02 ± 0.02 | 1.02 ± 0.02 |
pH @ 20°C | 8.0 ± 1.0 | 8.0 ± 1.0 | 8.0 ± 1.0 |
Viscosity @ 20°C #4, 60 rpm | 1,400 ± 200 cSt | 1,200 ± 200 cSt | 900 ± 200 cSt |
Pour Point | Flows at 0°C | Flows at 0°C | Flows at 0°C |
*Foam Expansion | > 7 | > 7 | > 7 |
*Foam Drainage 25% | > 5 minutes | > 5 minutes | > 5 minutes |
Expansion & Drainage values depend on the equipment & the application conditions
Certified Vertical Turbine Fire Pump
RATINGS
Rated Capacity (US GPM) | Rated Pressure Range (PSI) |
---|---|
50 | 42-188 |
100 | 52-173 |
150 | 87-254 |
200 | 84-246 |
250 | 50-235 |
300 | 69-86 |
400 | 66-82 |
500 | 63-80 |
750 | 84-108 |
1000 | 81-99 |
1250 | 105-283 |
1500 | 108-135 |
Certified Fuel Tank
DESCRIPTION
NAFFCO certified primary containment tank offers you a reliable solution for your fuel storage requirements related to fire pump diesel engine applications as required by NFPA 20. Design and fabrication of these tanks are done as per UL standard (UL 142), and installation and use shall be in accordance with NFPA 30.
Each tank is subjected to thorough structural inspections and leakage test as specified by the design standard. The tanks that successfully pass the inspection and test are labelled as per UL specifications confirming their UL certification. These cylindrical, horizontally mounted, tanks are provided with necessary fittings and openings to facilitate quality service at field.
SPECIFICATION
Tank Capacity (US Gallons) | Dia. (mm) | Length (mm) | Leg Width (mm) |
---|---|---|---|
70 | 600 | 1050 | 430 |
150 | 800 | 1250 | 575 |
250 | 1000 | 1325 | 720 |
310 | 1070 | 1450 | 768.5 |
Certified Jockey Pump Controllers
DESCRIPTION
NAFFCO Jockey Pump Controllers are listed by Underwriters Laboratories (UL file number E309408), in accordance with UL 508A (Standard for Industrial Control Panel), NFPA 70 (National Electric Code) and NEMA Standards.
Power ratings vary from 1.5 to 40 horsepower, 380 to 415 volts, 50 or 60 Hz.
Only high quality UL listed or UL recognized components are used in these panels to guarantee the best possible reliability. Also high quality UL listed enclosures are used.
The controller is completely wired, assembled and tested at the factory before shipment, and ready for immediate installation.
SPECIFICATION
NFY-JDO1 – Direct On Line Type
Power (HP) | Rated Voltage (VAC) | Frequency (Hz) | Rated Current (A) | Short Circuit Current (kA) | Enclosure Size (mm) |
---|---|---|---|---|---|
1.5 | 380-415 | 50 or 60 | 3.3 | 5 | 500 (H) x 400 (W) x 250 (D) |
2 | 380-415 | 50 or 60 | 4.3 | 5 | 500 (H) x 400 (W) x 250 (D) |
3 | 380-415 | 50 or 60 | 6.1 | 5 | 500 (H) x 400 (W) x 250 (D) |
5 | 380-415 | 50 or 60 | 9.7 | 5 | 500 (H) x 400 (W) x 250 (D) |
7.5 | 380-415 | 50 or 60 | 14 | 5 | 500 (H) x 400 (W) x 250 (D) |
10 | 380-415 | 50 or 60 | 18 | 5 | 500 (H) x 400 (W) x 250 (D) |
15 | 380-415 | 50 or 60 | 27 | 5 | 500 (H) x 400 (W) x 250 (D) |
20 | 380-415 | 50 or 60 | 34 | 5 | 500 (H) x 400 (W) x 250 (D) |
25 | 380-415 | 50 or 60 | 44 | 5 | 600 (H) x 500 (W) x 250 (D) |
30 | 380-415 | 50 or 60 | 51 | 5 | 600 (H) x 500 (W) x 250 (D) |
40 | 380-415 | 50 or 60 | 66 | 5 | 600 (H) x 500 (W) x 250 (D) |
NFY-JSD1 – Star – Delta Open Transition Type
Power (HP) | Rated Voltage (VAC) | Frequency (Hz) | Rated Current (A) | Short Circuit Current (kA) | Enclosure Size (mm) |
---|---|---|---|---|---|
1.5 | 380-415 | 50 or 60 | 3.3 | 5 | 500 (H) x 400 (W) x 250 (D) |
2 | 380-415 | 50 or 60 | 4.3 | 5 | 500 (H) x 400 (W) x 250 (D) |
3 | 380-415 | 50 or 60 | 6.1 | 5 | 500 (H) x 400 (W) x 250 (D) |
5 | 380-415 | 50 or 60 | 9.7 | 5 | 500 (H) x 400 (W) x 250 (D) |
7.5 | 380-415 | 50 or 60 | 14 | 5 | 500 (H) x 400 (W) x 250 (D) |
10 | 380-415 | 50 or 60 | 18 | 5 | 500 (H) x 400 (W) x 250 (D) |
15 | 380-415 | 50 or 60 | 27 | 5 | 500 (H) x 400 (W) x 250 (D) |
20 | 380-415 | 50 or 60 | 34 | 5 | 500 (H) x 400 (W) x 250 (D) |
25 | 380-415 | 50 or 60 | 44 | 5 | 600 (H) x 500 (W) x 250 (D) |
30 | 380-415 | 50 or 60 | 51 | 5 | 600 (H) x 500 (W) x 250 (D) |
40 | 380-415 | 50 or 60 | 66 | 5 | 600 (H) x 500 (W) x 250 (D) |
Certified Diesel Fire Pump Controllers
DESCRIPTION
NAFFCO Microprocessor Based Fire Pump Diesel Engine Controller are listed by Underwriters Laboratories (UL file number EX15064), in accordance with UL 218 (Standard for Fire Pump Controller), UL 508a (Standard for Industrial Control Panel), NFPA 20 (National Fire Protection Association Pamphlet 20 – Standard for Centrifugal Fire Pumps), NFPA 70 (National Electric Code) and NEMA standards.
Also approved by FM approvals (Factory Mutual), in accordance with FM standard 1321 / 1323 (Standard for Fire Pump Controller).
Power ratings suitable for 12/24 volts DC operating voltage, 110 / 220 volts AC input voltage, 50/60 Hz. These controllers are compatible with most types of diesel engines used for fire pump applications.
Only high quality UL listed or UL recognized components are used in these panels to guarantee the best possible reliability. Also high quality UL listed enclosures are used.
This controller is completely wired, assembled and tested at the factory before shipment, and ready for immediate installation.
SPECIFICATION
DC Voltage (VDC) | Line Voltage (VAC) | Enclosure Size (mm) |
---|---|---|
12 | 220/110 | 900 (H) x 600 (W) x 300 (D) |
24 | 220/110 | 900 (H) x 600 (W) x 300 (D) |
Certified Electric Fire Pump Controllers
DESCRIPTION
NAFFCO Microprocessor Based Electric Motor Controllers for fire pumps are listed by Underwriters Laboratories (UL file number EX15064), in accordance with UL 218 (Standard for Fire Pump Controller), UL 508a (Standard for Industrial Control Panel), NFPA 20 (National Fire Protection Association Pamphlet 20- Standard for Centrifugal Fire Pumps), NFPA 70 (National Electric Code) and NEMA standards.
Also approved by FM approvals (Factory Mutual), in accordance with FM standard 1321 / 1323 (Standard for Fire Pump Controller).
Power ratings vary from 40 to 400 horsepower, 230 / 380 / 415 VAC, 50/60 Hz.
Only high quality UL listed or UL recognized components are used in these panels to guarantee the best possible reliability. Also high quality UL listed enclosures are used
This controller is completely wired, assembled, programmed and tested at the factory before shipment, and ready for immediate installation.
SPECIFCATION
MODEL – STARTING TYPE
NFY-DOM1 – Direct On Line
Motor Power (HP) | Rated Voltage (V) | Frequency (Hz) | Rated Current (A) | Short Circuit Current (kA) |
---|---|---|---|---|
15 | 380 – 415 | 50 / 60 | 27 | 100 |
20 | 34 | |||
25 | 44 | |||
30 | 51 | |||
40 | 66 | |||
50 | 83 | |||
60 | 103 | |||
75 | 128 | |||
100 | 165 | |||
125 | 208 | |||
150 | 240 | |||
200 | 320 | |||
250 | 403 | |||
300 | 482 | |||
350 | 560 | |||
400 | 636 |
NFY-SDM1 – Star Delta Open Transition
Motor Power (HP) | Rated Voltage (V) | Frequency (Hz) | Rated Current (A) | Short Circuit Current (kA) |
---|---|---|---|---|
15 | 380 – 415 | 50 / 60 | 27 | 100 |
20 | 34 | |||
25 | 44 | |||
30 | 51 | |||
40 | 66 | |||
50 | 83 | |||
60 | 103 | |||
75 | 128 | |||
100 | 165 | |||
125 | 208 | |||
150 | 240 | |||
200 | 320 | |||
250 | 403 | |||
300 | 482 | |||
350 | 560 | |||
400 | 636 |
AUTOMATIC POWER TRANSFER SWITCH
Motor Power (HP) | Rated Voltage (V) | Frequency (Hz) | Rated Current (A) | Short Circuit Current (kA) |
---|---|---|---|---|
15 | 380 – 415 | 50 / 60 | 27 | 100 |
20 | 34 | |||
25 | 44 | |||
30 | 51 | |||
40 | 66 | |||
50 | 83 | |||
60 | 103 | |||
75 | 128 | |||
100 | 165 | |||
125 | 208 | |||
150 | 240 | |||
200 | 320 | |||
250 | 403 | |||
300 | 482 | |||
350 | 560 | |||
400 | 636 |
AUTOMATIC POWER TRANSFER SWITCH
NFY-ATS – Auto Transfer Switch
Power Rating | 15 – 400 HP |
---|---|
Frequency | 50/60 Hz |
Rated Voltage | 380 – 415 V |