DESCRIPTION
The Alpha 5000 System is an auto-aligning, self-correcting infrared beam smoke detector. Up to 2 detector heads can report to a single ground level controller. In addition, each system controller houses two pairs of fire and trouble relays, one per detector. Once the detector head is installed, using the easyfit mounting system an integral LASER can be activated. This allows the reflective prism to be located quickly and with confidence.
SPECIFICATION
Primary Input Power | 14 to 36 V DC |
---|---|
Standby Current (Depending On Number Of Detector Heads) | Low Current : 5 mA to 8.5 mA @ 24 V DC High Current : 37 mA @ 24 V DC |
Alarm Current | 5 mA to 8.5 mA @ 24 V DC depending on number of detector heads used |
Relay Contacts | 1 A @ 30 V DC Resistive |
Reset Time | 5 seconds maximum |
Start Up Time | 45 seconds |
Optical Wavelength | 850 nm |
Temperature Rating UL Listed | 0°C to 38°C |
Primary Input Power | 14 to 36 V DC |
IP Rating | IP54 |
Dimension (W x H x L) & Weight | |
Head | 134 mm x 134 mm x 131 mm, 1470 g |
Controller | 202 mm x 87 mm x 230 mm, 1470 g |
Prism | 100 mm x 9.5 mm x 105 mm |
FEATURES
- Up to 2 Detector Heads reporting to One Ground Level Controller
- Built in Laser assisted prism mounting
- Auto-Alignment 2 to 4 minutes per head
- AutOptimise: Auto-Correction due to building shift
- Built-in electronic UL/ULC obscuration-acceptance fire test
- Contamination compensation
- Separate Trouble and Alarm relays for each of the 2 channels
- Password protected settings
- Programmable alarm thresholds: 10% – 60% in 1% increments
- Programmable Fault and Alarm delay: 2-30 Seconds